Abstract

Abstract In cold climates, a building ventilation rate must be selected to control contaminants adequately but must not be excessive. Measurements of natural gas (total hydrocarbons), hydrogen sulfide, and carbon monoxide in 16 gas compressor buildings containing 42 compressors (up to 2000 HP each) showed total hydrocarbons to be the critical material requiring additional control by ventilation (primary control is by containment). Ventilation rates were estimated by tracer gas decay (Freon 12®, measured by infrared analyser), thus hydrocarbon leakage rates could be calculated. Of the compressors studied, 95% had leakage rates below 130 Ipm of natural gas. The principles of dilution ventilation allowed calculation of a recommended ventilation rate which would control natural gas hydrocarbons to less than 1000 ppm, the present health standard, in the majority of the Company's gas compressor buildings (130 mYmin per operating compressor). Results of the study include implementation of a leak detection and ma...

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.