Abstract

Due to the power quality problems and the use of some nonlinear loads such as soft starters, rectifiers, and frequency converters, the circuit current will contain complicated harmonic components, which may affect the identification accuracy of arc fault. Aiming at the interferences of power supply harmonics and nonlinear load noise, a kind of recognition method based on kernel principal component analysis (KPCA) and firefly algorithm optimized support vector machine (FA-SVM) was proposed. KPCA was used to separate the harmonics and load noise interferences in the voltage and current signals. Kurtosis and skewness of the fifth and sixth principal components were used as arc fault features. The FA-SVM was designed to recognize arc fault. The arc fault experiments were carried out under complicated harmonic conditions. The effectiveness of the presented method was verified by experiments.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.