Abstract
This paper discusses transmission line operating experience on the 140,000-volt isolated neutral system of the Consumers Power Company, Michigan. Careful inspections and tests have been made to determine the conditions existing relative to insulator flashover and the findings and results are shown by tables and curves. Ground resistance or soil conditions appear to have a very decided effect on the number of flashovers on the various lines. The necessity of providing suitable arc protection to the line conductors is shown, as is also the soundness of certain theories and recommendations for increasing the reliability of transmission lines, based upon laboratory experiments.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Transactions of the American Institute of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.