Abstract

In distributed control system (DCS), computation tasks, which usually reside in different nodes and communicate with one another to accomplish a common goal, have to be executed timely. Therefore, there is a need for special-purposed real-time industrial networks. Foundation Fieldbus (FF) is characterized by explicitly distinguishing between periodic and aperiodic messages. Centralized Media Access Control (MAC) is utilized by FF to support periodic messages, and distributed MAC to support aperiodic messages. It is indicated that FF's current mechanism using Pass Token (PT) priority and PT circulation period cannot effectively guarantee the real-time requirement of important aperiodic messages. A detailed analysis shows the method of computing Actual PT Circulation Period (APTCP) should be improved. An improved method of computing APTCP is proposed in this paper, and then a method of determining Setting PT Circulation Period (SPTCP) is presented accordingly. In the end, simulation validates the effect of the improved method on the real-time performance of urgent aperiodic messages in FF.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.