Abstract

AbstractThis paper proposes a real‐time hot‐spot monitoring method for three‐phase two‐winding oil‐filled transformers under steady‐state conditions, where the corresponding test certificates are not accessible to the customers. For this purpose, the separate determination of iron‐core and copper losses is achieved by real‐time measuring of voltages and currents in both primary and secondary sides and also employing nameplate data of the transformer, including the winding resistances. Subsequent calculations based on IEEE Std C57.110‐2018 provide the top‐oil and hot‐spot temperatures. It is shown that the estimated top‐oil and winding hot‐spot temperatures and also load and no‐load losses match with the measured ones with the maximum difference of 3.5%, 2%, 2.7%, and 9%, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.