Abstract
It is possible to capture the required travelling wave information contained in fault transients using wavelet transform. This paper presents practical real time testing for the high impedance fault (HIF) detection algorithm based on real time accidents data. The proposed scheme is implemented for HIF detection in extra high voltage transmission lines. The classifier is based on an algorithm that uses recursive method to sum the absolute values of the high frequency signal generated over one cycle and shifting one sample. Characteristics of this scheme are analyzed by extensive real time studies that clearly reveal that this technique can accurately detect HIFs in the EHV transmission lines within only half a cycle from the instant of fault occurrence. The reliability of this scheme is not affected by different fault conditions such as fault distance and fault inception angle.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.