Abstract

This paper presents an implementation of an IEC 61850-based real-time co-simulation platform for verification of the performance of a volt-VAR optimization (VVO) engine for smart distribution networks. The proposed VVO engine is able to minimize grid loss, volt-VAR control asset operational costs, and conservation voltage reduction operational costs through its comprehensive objective functions, weighted by fuzzification using advanced metering infrastructure (AMI) data. The optimization engine receives the AMI data stream through measurement aggregators. Moreover, it sends control commands to volt-VAR control components modeled in real-time digital simulator (RTDS) through DNP.3 protocol. To check the performance and the precision of proposed VVO, a fault scenario is imposed upon the system. IEC 61850 GOOSE messages are generated and sent to change the status of specified breakers, while the VVO engine receives system reconfiguration commands via IEC61850 Manufacturing Message Specification (MMS) protocol. The results of the study on 33-node feeder showed adequate performance of proposed VVO in grid operating scenarios.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.