Abstract
Domestic air conditioners (AC) are a major source of energy consumption. Based on real time data, the input/output dynamics between electronic expansion valve opening degrees (EEVOD) and evaporator outlet air (supply air) temperature is modeled in this paper. Considering an on/off scenario, the outer loop provides two different references to the inner loop based on heating/cooling needs. This supply air temperature (SAT) influences the room model with ambient temperature and wall dynamics (ordinary differential equations simulated in MATLAB). With safety constraints for superheat (SH) and rate constraints on EEVOD, a multi parametric model predictive controller (mpMPC) is designed to control SAT. A proportional integral cascade control scheme is designed to compare the performance of the mpMPC scheme. In hardware in loop (HIL) environment, both controllers are tested under ambient temperature based disturbance. Using power spent and thermal comfort quantization, it is observed that mpMPC scheme outperforms traditional control strategy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.