Abstract
A combined reactive power compensation method of a static VAr compensator (SVC) and a series active filter is described for unbalanced three-phase four-wire distribution feeders with harmonic distortion. The SVC which consists of Δ-connected thyristor-controlled reactors, Y-connected thyristor-controlled reactors and passive filters, acts as a classic reactive power compensator for load balancing and power factor correction. The small rating active filter is used to improve the filtering characteristics of the passive filter in the SVC and suppress possible resonance between the system impedance and the passive filter. Simulation results performed by the electromagnetic transients program show that the proposed reactive power compensation configurations can effectively balance currents, correct power factor and eliminate harmonic currents.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.