Abstract

Ratio correction factor and phase displacement of instrument transformers vary with the values of the external burden connected to the secondary of the transformers. Using the values measured at two burdens of the instrument transformers, the ratio correction factor and phase displacement at arbitrary burdens are theoretically obtained without any additional measurement. This is based on a theoretical analysis of the equivalent circuits of the instrument transformers. The validity of the methods was verified by comparing the theoretical value with measured value for several instrument transformers with different accuracy.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.