Abstract

ABSTRACTA novel lumped parameter approach is introduced to predict data center exergy destruction due to airflow mixing, resulting in a speedup of several orders of magnitude compared to detailed computational fluid dynamics (CFD) simulations. Both lumped parameter and detailed CFD methods agree within 8.5% for 11 test cases on an example data center. A significant time-saving design strategy is also introduced using two detailed CFD simulations to predict bulk flow parameters, and then applying lumped parameter analysis on flow-independent design parameters. The strategy shows agreement within 0.39% when computer room air conditioner (CRAC) supply temperature is varied from 12–20°C.