Abstract

The need for a reliable and continuous power source to supply electrical loads is very important. In order for continuous electricity supply, a system of Automatic Transfer Switch - Automatic Main Failure (ATS - AMF) is needed. This system will automatically divert electrical power from the main PLN source to a backup source. The stages in the design of this tool include ATS-AMF planning, component assembly process, and box panel assembly. The result is a 380 V, 50 Hz ATS/AMF panel based on the LS Master K120s PLC which is supported by both manual and automatic operating systems. For the AMF system using the PLC LS Master K120s, the generator set is set for 3 seconds after the supply from PLN goes out and will immediately supply electrical energy after 5 minutes after the generator is running. When PLN returns to normal for 5 minutes the generator set will be separated from the system, the generator will cool down, then the generator will stop. The ATS-AMF system works as described for which it was designed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.