Abstract

Monitoring the switching times of circuit breakers is important in the condition assessment of the operating mechanism. Although methods exist for this, they are not applicable to existing plant without retrofitting. Recent research shows that arcing produces impulsive radio-frequency radiation. Using direct digital sampling of the antenna signals, impulses from operating circuit breakers (CBs) may be recorded. From timing analysis of the received impulses, the interpole switching time of the CB can be measured. Results of this method are shown for a field trial on a 132-kV SF/sub 6/ CB attached to a capacitor bank. The relationship between the opening and closing impulses is discussed. This method of timing measurement can be applied to an energized CB. Measurement of the interpole switching times is completely noninvasive, whereas the overall switching time requires a clamp CT fitted on the CB wiring.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.