AbstractAs part of an effort to characterize the uncertainties associated with heat flux measurements in a fire environment, an uncertainty analysis example was performed using measurement data from a room corner surface products test that followed the guidelines of ISO 9705. Equations to model the heat transfer at the surface of a Schmidt‐Boelter (thermopile) type total heat flux gauge were selected for use to calculate the incident radiative flux from a total heat flux measurement. The effects of the heat flux measurement uncertainty sources were evaluated by conducting an uncertainty propagation on the resulting equation for incident radiation. For the model equations and the example conditions selected, the free‐stream temperature estimate and the heat flux gauge calibration constant were determined to be major uncertainty contributors. The study demonstrates how to systematically identify major sources of uncertainty for the purpose of reducing total uncertainty and thereby enhancing experiment design. Published in 2003 John Wiley & Sons, Ltd.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.