Abstract

It is well known that EMI arises from any operation that interrupts or changes an electrical current. During switching operations in substations, very fast, high field transients occur which can adversely affect, whether by radiated or conducted interference, the electronic equipment in equipment rooms unless it is adequately protected. The environment in which this equipment is installed therefore needs to be fully characterised in terms of electromagnetic interference levels. With this knowledge it is possible to provide adequate immunity for electronic equipment, and design efficient, effective and reliable protection, control and monitoring systems. The paper identifies two areas where the IEC 61000-4-10 Standard appears to be deficient. These are the required test frequencies of 10 kHz and 10 MHz, and testing at these frequencies are recommended at a repetition rate as determined by the formula given in the Standard.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.