Abstract
Hydrogen refueling stations (HRSs) are among the most important infrastructures for fuel cell vehicles. However, the safety issue of HRSs has become a key constraint to the wide application and development of hydrogen energy. This article presents a quantitative risk assessment of the first liquid HRS (LHRS) in China and conducts a comprehensive assessment in terms of both individual (IR) and societal risks (SRs). The results showed that both the IRs and SRs related to the LHRS exceeded the risk acceptance criteria. The rupture of the flexible hose of the dispenser and the leak from the compressor are the main contributors to these risks. On the other hand, implementing appropriate mitigation measures on the level of the LHRS dispenser and compressor, including the addition of breakaway couplings in the flexible hose of the dispenser, the installation of hydrogen detection sensors, the arrangement of automatic and manual emergency shutdown buttons, and the elevation of the compressor, is capable of reducing the risk of the LHRS to be within the risk acceptance criteria.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.