Abstract

This paper presents a quantitative risk assessment (QRA) study of an oil-gas-hydrogen-electricity integrated energy station in China. A comprehensive assessment of the station was made in terms of consequences and risks, respectively. Consequence analysis shows that the severity of hazardous chemical leakage accidents in the station is in the order of natural gas, hydrogen, gasoline, and diesel fuel, especially in the liquefied natural gas (LNG) and compressed natural gas (CNG) storage tank areas, which may cause major accidents in the event of leakage. The results of the risk assessment showed that the individual and societal risks of the integrated oil-gas-hydrogen-electricity energy station exceeded the risk acceptance criteria. Moreover, the catastrophic rupture of LNG and CNG storage tanks is the main cause of the unacceptable risk. Additional mitigation measures for them, mainly including the installation of emergency manual shut-off valves, the installation of combustible gas detection and alarm devices, and pressure relief protection devices, can effectively reduce the risk to an acceptable level.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.