Abstract
The thermal behaviour of a building is often underestimated or neglected during its construction and operation stages. In recent years, the heat flux meter (HFM) method has been commonly used to determine the U-value, a key parameter for assessing the thermal quality of the building envelope in steady-state conditions. However, this non-invasive test takes at least 72h to execute, the accuracy is 14–28%, and it is not reliable for non-homogeneous building elements. An alternative technique is based on infrared thermography (IRT). Although it is generally used for qualitative analysis, quantitative internal IRT methods may also be adopted for in-situ measurement of the U-value. This research presents a method for determining in-situ U-values using quantitative internal IRT with a deviation of 1–2% for single-leaf walls and 3–4% for multi-leaf walls. It takes 2–3h and can be used to provide information about the building envelope for the future refurbishment of existing buildings or to check the thermal behaviour of new building façades according to their design parameters.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.