Abstract

There is growing evidence that viruses responsible for pandemics, such as Middle East respiratory syndrome and severe acute respiratory syndrome, are mainly spread through aerosols. Recommendations have been introduced to reduce the transmission risks of virulent airborne viral particles by increasing ventilation rates, expressed in air changes per hour (ACHs), effectively improving the dilution of pathogens via mechanical ventilation. However, infrastructural and operational costs associated with upgrades of building heating, ventilation, and air conditioning systems make these solutions expensive. It is well documented that Ultraviolet Subtype C (UVC) disinfection can help lower exposure risks by inactivating viruses and the performance of such solutions can translate into equivalent ventilation. Here, we present the first framework to extract the optimal UVC requirements to improve facility management yet ensuring compliance with ventilation guidelines at lower energy costs. The Kahn–Mariita (KM) model considers the air quality of shared enclosed spaces over time by supplementing the existing mechanical ventilation with localized UVC air treatment and includes variables such as room size, occupancy, existing ventilation, and target equivalent ACH. For example, the model applied to a conference room shows that a UVC chamber with recirculation rates of 160 m3/h increases ventilation from an ACH 3 to 7.9 and reduces the room’s reset time from 46 to <10 min with as little as 1 W. Recirculation rates of 30 m3/h however offer no benefits beyond 200 mW, with an eACH of 3.9 and reset time of 31 min. The first finding is that single-pass disinfection is not an appropriate metric of performance, i.e., low recirculation rates increase single-pass disinfection, and, however, only treats a portion of the space volume within a given time, limiting the overall performance. Conversely, higher recirculation rates decrease single-pass disinfection but treat larger portions of air, potentially multiple times, and are therefore expected to lower the transmission risk faster. The second result is that for fixed amounts of recirculating air flow, increasing UVC power helps with diminishing return, while for a fixed UVC power, increasing the recirculating air flow will always help. This dynamic is particularly important toward optimizing solutions, given the constraints system engineers must work with, and particularly to design for end-user benefits such as increased occupancy, in-dwelling time, or reduction of shared-space reset time.

Highlights

  • The current COVID-19 crisis has highlighted the lack of readiness to manage pandemics globally and the need for solutions to disinfect the air, which is dominantly responsible for the transmission of pathogens (Zhang et al, 2020a) such as SARS-CoV-2 (Nardell, 2021)

  • The approach of eACH consists in assigning a quantitative measure, which consists of localized air treatment in poorly ventilated rooms with Ultraviolet Subtype C (UVC) light to reduce airborne contaminant concentrations, which corresponds to the same air quality microbiologically to that of increased mechanical ventilation

  • The model is not focused on the LRV of this problem since it considers the time to reach a single LRV (90% reduction), but it is useful to show that the relative benefits of the UVC dose on the eACH decrease with an increase in dose

Read more

Summary

Introduction

The current COVID-19 crisis has highlighted the lack of readiness to manage pandemics globally and the need for solutions to disinfect the air, which is dominantly responsible for the transmission of pathogens (Zhang et al, 2020a) such as SARS-CoV-2 (Nardell, 2021). Ultraviolet Subtype C (UVC) radiation, emitted at 200–280 nm with germicidal effect and being able to disrupt nucleic acids (RNA or DNA) (Yin et al, 2013), can be used to disinfect the air, managing disease outbreak (Reed, 2010). Studies carried out during the COVID-19 pandemic have demonstrated that UVC can rapidly inactivate SARS-CoV-2 (Storm et al, 2020) even at high viral titers (Heilingloh et al, 2020). The use of UVC to ensure clean air will save energy by warranting reduced building heating, ventilation, and air conditioning (HVAC) energy demand (Aviv et al, 2021)

Methods
Findings
Discussion
Conclusion

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.