Abstract

Recent evidence available in the literature has highlighted that the high-energy consumption rate associated with air conditioning leads to the undesired “overcooling” condition in arid-climate regions. To this end, this study quantified the effects of increasing the cooling setpoint temperature on reducing energy consumption and CO2 emissions to mitigate overcooling. DesignBuilder software was used to simulate the performance of a generic building operating under the currently adopted ASHRAE HVAC criteria. It was found that increasing the cooling setpoint temperature by 1 °C will increase the operative temperature by approximately 0.25 °C and reduce the annual cooling electricity consumption required for each 1 m2 of an occupied area by approximately 8 kWh/year. This accounts for a reduction of 8% in cooling energy consumption compared to the ASHRAE cooling setpoint (i.e., t_s = 26 °C) and a reduction in the annual CO2 emission rate to roughly 4.8 kg/m2 °C. The largest reduction in cooling energy consumption and CO2 emissions was found to occur in October, with reduced rates of approximately–1.3 kWh/m2 °C and −0.8 kg/m2 °C, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.