Abstract
To verify the beneficial use of UHPC in the highly stressed region of column-slab connections, a total of ten punching tests on reinforced concrete slabs were performed. All interior column-slab connections included double-headed studs as shear reinforcement. Nine test specimens were in addition strengthened by fibre-reinforced Ultra High Performance Concrete (UHPC) units. These elements were built in around the columns in the slab compression zone, replacing there the normal strength concrete (NSC). UHPC units with three different diameters were applied. To allow for a flexible combination of UHPC unit and double-headed studs, most of the UHPC units were separated into four parts with joints in between and were provided with channels for the double-headed studs. The slabs including a UHPC element reached significantly higher failure loads than the test specimens without such an element. In the slabs including the UHPC units with smaller diameter, a clear punching shear failure outside the elements was observed. In the case of the larger UHPC units, significant cracks occurred inside the elements, indicating the initiation of a failure of the UHPC.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.