Abstract

Boiling hysteresis is a side effect that usually occurs with overshot temperature before steady boiling, often noted as a start-up problem. This phenomenon tends to emerge when porous surfaces are used to enhance boiling heat transfer performance. It is important to reduce or eliminate hysteresis before various micro−/nanoporous surfaces can be deemed acceptable in the thermal management industry. In this study, a two-layer composite surface (TLCS) with a copper forest structure at the bottom and micro-nano biporous structure at the top showed good enhancement at a heat transfer coefficient of 340% and critical heat flux of 67% compared to a plain copper surface with water as the working fluid at atmosphere. However, boiling hysteresis occurred on TLCS; the highest wall superheat temperature difference between steady boiling and the start-up process was approximately 13.5 K at 140 W cm−2. When TLCS was modified with Polytetrafluoroethylene (PTFE), the temperature difference at the same heat flux was less than 0.5 K, demonstrating that the boiling hysteresis phenomenon was successfully eliminated.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.