Testing the piping of a new hospital showed that the drinking water was contaminated with Pseudomonas aeruginosa. Because of pollution the plumbing system was treated with oxidizing biocides and air-water flushing for several times, unfortunately without stopping the bacterial recontamination. The reasons were firstly stagnation due to dead legs in the piping system, oversized pipes, very low water exchange rates and the installation of a catch water system, secondly low flow velocity because of low water pressure. After these sources of recontamination had been repaired, chlorine dioxide sanitization could be stopped successfully

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.