Abstract
The numerical study of the pseudo transient thermal behavior of an earth-to-air heat exchanger (EAHE) for three cities in México is presented. The climate conditions correspond to the warmest day in summer and the coldest day in winter for: extreme weather (Juárez city, Chihuahua), mild weather (México city, D.F.) and hot weather (Mérida, Yucatán). The simulations of the EAHE were done in an in-house code based on the finite volume method. Hourly simulations were done for four Reynolds numbers (100, 500, 1000, 1500) through one day. In Juárez city, the EAHE worked correctly for cooling and heating purposes during the whole day. For Mérida and México City the EAHE did not work during certain periods. The maximum cooling potential provided by the EAHE was 17.4, 10.2 and 10°C in Juárez, Mérida and México City, respectively. The maximum heating potential provided by the EAHE was 6.3, 12.5 and 3.2°C in Juárez, Mérida and México City, respectively. Such cooling and heating effects help to improve the thermal comfort inside a building located in this type of climates.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.