Abstract

The article presents a measurement study of the causes of damage to medium-power and medium-voltage motors used to drive water intake pumps for the city. The user of the pumping station used a low-voltage frequency converter to regulate the pump output, which was powered by a 6/0.4 kV transformer. The voltage behind the converter was increased via a 0.4/6 kV transformer and powered the pump motors via cable lines. Within 2 years from the implementation of converter the insulation of the winding front connections have been damaged in 3 motors. It appears that the permissible instantaneous voltage was almost twice exceeded.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.