Abstract

This paper concerns the addition of the few critical elements of a protection system to the Electromagnetic Transients Program (EMTP), which is one of the most widely used programs for the simulation of transients in power systems. It contains models for almost every major power system component. A protection system consists of instrument transformers, relays, and circuit breakers. Models for current transformers (CTs) and capacitor voltage transformers (CVTs) are developed, validated, and incorporated in the EPRI/DCG EMTP Version 2.0. The user can define the values of the CT and CVT parameters. Total FORTRAN capability has been added to the EMTP; new subroutines and an inbuilt structure to allow the linking of user-defined FORTRAN subroutines with the main EMTP are explained. This capability is necessary to simulate computer relay algorithms. These new features in the EMTP together constitute the critical elements of a protection system. Thus, it is now possible to simulate the dynamic interactions between a power system and a protection system. >

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.