In this paper, a new concept of wavelet transform (WT)-based technique is introduced to detect various types of shunt faults in a wind farm integrated double circuit transmission line. The information of fault contained in the current signals of both circuits is captured using wavelet transform. The fifth level detail coefficients of current signals of both circuits are then calculated which aspires at detecting the fault and identifying the faulty phase. Test results show that the proposed fault detection scheme effectively detects the fault and discriminates the faulted phase. The proposed technique offers primary protection to the total transmission length using data recorded at relaying location only. The fault cases such as variation in fault type, fault resistance, close-in faults, remote-end faults, transforming faults, multi-location faults and cross-country faults are taken into account.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.