Abstract

The high phase order transmission demonstration project is described. An existing 115 kV double-circuit transmission line was electrically reconfigured into a single-circuit, six-phase transmission line for this purpose. A description is given for different computer applications used in all stages of design, operation, and postoperation analysis. The complex multirelay microprocessor-based protection system is discussed. The multirelay microprocessor protection system was tested for many typical fault combinations using a computer controlled fault simulator. Currents and voltages were calculated using the Electromagnetic Transient Program (EMTP).< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.