Abstract

It is shown experimentally that using forced-convection boiling of dielectric coolants of the Novec 649 Refrigerant subcooled relative to the saturation temperature makes possible removing heat flow rates up to 100 W/cm2 from modern supercomputer chip interface. This fact creates prerequisites for the application of dielectric liquids in cooling systems of modern supercomputers with increased requirements for their operating reliability.