Abstract
The Refinery and petrochemical production facilities process and produce the gaseous and liquid flammable hydrocarbons under the pressure conditions. In case of any failure, improper design or human mistake there can be autonomous and independent pressure relieve systems activated to release the pressure to the flare systems to protect the equipment against the overpressure, damages and other consequences. The paper describes the failure occurred at the Steam Cracker unit in Litvinov, Czech Republic in 2015. As a result of a loss of cooling followed by loss of reflux event, the pressure relief system of the Propylene Column was activated whereas the pressure relief valves opened up and chattered, resulting in loosening of flange bolts and loss of containment. The release of the propylene vapor ignited, resulting in subsequent explosion and fire at the Propylene Column area. The interruption of steam and instrument air supply caused by the fire damages led to the other extensive fire of four pyrolysis heaters. The extraordinary event description, root cause analysis, investigation as well as the corrective actions are introduced and analyzed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of Loss Prevention in the Process Industries
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.