Abstract

This paper deals with the possibility of ferroresonance occurence in the interaction between circuit breakers and inductive instrument transformers. Existing standards lack guidance on testing for ferroresonant behaviour. The paper proposes a standardized testing procedure and presents measurements on a full-scale system. EMTP simulations complement the measurements for a broader network topology analysis, i.e. circuit breaker capacitance combinations. EMTP simulations are validated for a 170 kV voltage transformer and a combined instrument transformer, showing accuracy within 10%. The paper also extends the EMTP modelling application to a 420 kV voltage power transformer during design phase, ensuring it doesn't experience ferroresonance. This study offers a practical approach for testing and simulating ferroresonance in inductive instrument transformers, contributing to the safe operation of power networks.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.