Abstract

Prony's method is a technique for estimating the modal components present in a signal. Every modal component is defined by four parameters frequency, magnitude, phase, and damping. This method is used to analyse earth fault currents in Petersen-coil-protected 20 kV networks. The variations of Prony's parameters in terms of some of the power systems characteristics (distance between the busbar and the fault, fault resistance and capacitive current of the whole network) are presented. It is shown that some of the Prony's parameters relating to the fault current transient may be useful to determine what kind of fault occurred, and where it occurred.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.