Abstract

Capacitive voltage transformer (CVT) in high and medium voltage system cannot be used for harmonic voltage measurement. A new method making use of capacitive taps in current transformer (CT) bushings is recommended here, this method can achieve the good precision of harmonic voltage measurement. Attention to potential transformer (PT) should be paid in special cases such as a resistor or nonlinear resistor is connected across the neutral point on primary side and ground. In such a case, the harmonic voltage measurement cannot reflect the real distortion of the system voltage.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.