Abstract

Through long-term (3 years) partial discharge (PD) tests on some component models for transformer insulation, the authors have revealed that transformer insulation has a threshold voltage, Vol below which no partial discharge will occur regardless of how long the voltage may last. The value of VO is more than 62.5 percent of a 50-percent probability PD inception voltage at one-minute ac test.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.