Abstract

This paper first derives a usable formula for frequency shift islanding detection methods on the basis of the parallel R , L , C load and the conclusions in current literature: the angle by which the total output current of the distributed resources (DR) units leads the point of common coupling (PCC) voltage must be conducted to have the same shifting direction as the load admittance angle during the variation of the frequency. According to the formula and multi-DR operation, the scenarios in which the classic frequency shift methods are applied to energy storage converters are analyzed. The results indicate that the setting of the angle by which the energy storage converter current leads the PCC voltage may need to be modified when running state changes. It results in the problems that the classic methods are not applicable for non-unity power factor (non-UPF) control and have to distinguish between generation mode and consumption mode for UPF control. On account of the problems, a coping strategy, i.e., an improved method, is proposed. The analyses indicate that the improved method is applicable in every state. The last simulations and experiments confirm the preceding conclusions.