Abstract
The activation of under frequency load shedding (UFLS) is the last automated action against the severe frequency drops in order to rebalance the system. In this paper, the setting parameters of a multistage load shedding plan are obtained and optimized using a discretized model of dynamic system frequency response. The uncertainties of system parameters including inertia time constant, load damping, and generation deficiency are taken into account. The proposed UFLS model is formulated as a mixed-integer linear programming optimization problem to minimize the expected amount of load shedding. The activation of rate-of-change-of-frequency relays as the anti-islanding protection of distributed generators is considered. The Monte Carlo simulation method is utilized for modeling the uncertainties of system parameters. The results of probabilistic UFLS are then utilized to design four different UFLS strategies. The proposed dynamic UFLS plans are simulated over the IEEE 39-bus and the large-scale practical Iranian national grid.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.