Abstract
This paper proposes a method of the probabilistic load flow calculation of islanded microgrid (IMG) with droop-controlled distributed generations (DGs). The deterministic load flow is calculated based on Newton Raphson method considering the droop characteristics of DGs. The Monte Carlo method is applied for the evaluation of probabilistic distribution of load flow variables. The stochastic models of distributed generating systems including wind turbines and photovoltaic (PV) systems are established. The load model is considered as following a normal distribution. The effectiveness and efficiency of the proposed method are tested on a modified IEEE33 test system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.