Abstract
The reactive nature of traditional under-frequency load shedding schemes can lead to delayed response and unnecessary loss of load. This work presents a proactive framework for power system frequency stability. Bayesian filters and synchrophasors are leveraged to produce predictions after disturbances are detected. By being able to estimate the future state of frequency corrective actions can be taken before the system reaches a critical condition. This proactive approach makes it possible to optimize the response to a disturbance, which results in a decrease in the amount of compensation utilized. The framework is tested via Matlab simulations based on Kundur’s Two-Area System, and the IEEE 14-Bus System. Performance metrics are provided and evaluated against other contemporary solutions found in literature. During testing this framework outperformed other solutions by drastically reducing the amount of load dropped during compensation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.