Abstract

The paper analyzes the levels of magnetic flux density in the apartment located above the 10/0.4 kV distribution transformer station. During the first magnetic field testing, it was concluded that in the case of the rated load of the transformers, increased values of magnetic flux density would occur in the apartment. The main sources of magnetic field in the apartment were the busbars and cable lines connecting the transformers and the 0.4 kV distribution cabinets. For that reason it is proposed to apply measures to reduce the levels of magnetic flux density, which are described in detail in the paper. After implementing the proposed measures, magnetic field testing in the apartment was repeated. The paper presents magnetic field testing results before and after the application of the measures and gives a conclusion regarding the effectiveness of the applied measures as well as regarding the compliance of the levels of magnetic flux density with the exposure limit prescribed by the current national regulations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.