Abstract
The paper presents a study of primary frequency control within the power system of Continental Europe (CE) including the dynamics of the high voltage direct current (HVDC) link between France and Great Britain (GB). The large-scale dynamic model of the CE system originally provided by ENTSO-E is extended with a more detailed representation of the whole HVDC interconnection. The dynamics of the GB synchronous area is also considered in the analysis, implementing a system equivalent suitable for primary frequency control studies. The opportunity of frequency containment reserve exchange between the two areas through the link is also investigated, considering supplementary frequency controls within the HVDC control system, namely synthetic inertia and fast frequency response. The overall system is then simulated in two different scenarios: a base case of all synchronous generation, and a reduced inertia scenario with the introduction of a given amount of non-synchronous generation share. The reference incident for the CE system of 3 GW loss is considered for the analysis. The specific effects on the frequency dynamics of the system in the different operating conditions are illustrated and discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.