Abstract

Water and swab samples were collected from 13 hospitals and analyzed for Legionella counts. Legionella was detected in eight out of 13 hospitals and in 22 of 130 water and swab-collected samples. A total of 72.7% of the strains were L. pneumophila ser. 1, 22.7% were L. pneumophila ser. 2-14, and 4.5% did not belong to any of these groups. AFLP typing of the L. pneumophila ser. 1 strains generated two distinguishable AFLP types. There was no significant correlation to the sample type with Legionella recovery. Legionella isolation was more likely to occur in the cooling towers than the water system. Water temperatures of 30–40°C seem to favor Legionella growth. Of the 265 serum samples taken from the medical and technical staff for the control of IgG titre, 89.4% were negative, 7.2% were positive, and for 3.4% the result was doubtful. No association between IgG titre and maximum observed level of Legionella occurrence was detected.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.