Abstract

Pressure gradient control is an effective technical measure to prevent the external pollution and cross-contamination from different clean areas of a multi-zone cleanroom, which played a key role for the quality control of cleanroom. In this paper, modelling analysis combined with experimental investigations conducted on a multi-zone cleanroom experimental platform. A series of investigations were conducted on the experimental platform with supply air volume variation by electronic frequency conversion on air-supply fan unit. The characteristics of cleanroom such as cleanliness, ventilation rate, pressure gradient were all measured. An energy-saving operation strategy for multi-zone cleanroom has been gained. Experimental investigations proved that the determined principle of pressure gradient setting is feasible for reliable and energy-saving operation. It is also proved through experiments that about 24.5% energy consumption decreased when adopted the operation strategy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.