Abstract
The pressure drop of subcooled flow boiling in a narrow tube was investigated experimentally using water as a coolant. Experiments were conducted at nearly ambient pressure under the conditions : tube inside diameter : 1 and 3 mm, tube length : 10∼100 mm, and water mass velocity : 7000∼20000 kg/m2s. The friction pressure drop ratio of subcooled flow boiling to non-heating water flow was examined by increasing the heat flux. The ratio begins to increase at the heat flux proposed by the Saha-Zuber correlation that the bubble begins to detach for 3 mm inside diameter tube, though the heat flux is higher than the Saha-Zuber heat flux for 1 mm tube. The ratio was further compared with the Bergles-Dormer correlation. The two phase friction multiplier of subcooled flow boiling was examined assuming the Ahmad void fraction and applied to the Lockhart-Martinelli (L-M) correlation. The abnormarity of the subcooled flow boiling in the case of 1mm inside diameter tube was confirmed in these discussions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TRANSACTIONS OF THE JAPAN SOCIETY OF MECHANICAL ENGINEERS Series B
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.