Abstract

The ground differential (GD) relay is used to detect internal ground faults on the power transformer windings and terminals. In fact, this relay is employed as a complement to the phase differential (PD) relay. However, its stability is affected by magnetic saturation in current transformers (CTs) cores so that the spurious differential current caused by CT saturation may lead to the relay malfunction. In this paper, by modifying the restraining current definition in a conventional method, an adaptive restrain method is proposed. To evaluate the proposed method performance compared with conventional method, a real 230/63 kV power transformer under a large number of internal fault, external fault and in rush current cases are simulated in PSCAD/EMTDC environment. It is worth noting that Jiles-Atherton (JA) model is utilized to simulate CTs. MATLAB software is used to implement and analyze these methods using obtained simulation. Obtained results show that the proposed method is quite superior to the conventional method, despite its simplicity.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.