Abstract

Tan δ (dissipation factor)data on Cable System B is updated to include the full 2-year 500/550 kV test program at Waltz Mill and the 10-month 765/800 kV extended test program. This data is analyzed, demonstrating no change with time of tan δ for the system. Particular attention is paid to the paper splice, which exhibits a thermoelectric stability limitation at the 765/800 kV level. The outstanding performance of the PP/C splice is emphasized. Consideration of the operation of a very highly stressed oil impregnated paper insulation HPOF pipe system at 765 kV is suggested, including potential single circuit transmission capacity calculations.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.