Abstract
The cabin concept is widely used for fire protection in the retail areas of many big public transport terminals in the Far East However, very little systematic experimental studies were reported to demonstrate the performance of the system. Preliminary experimental studies on performance of full cabins, with operation of the installed mechanical smoke exhaust and sprinkler system, were carried out. A cabin of length 3.5 m, width 4 m, and height 3 m was constructed with supply air flow rate adjusted by the door size. A smoke exhaust system and sprinkler system were installed. Small fires with lower heat release rates up to 1.3 MW was set up with wood crib. Both normal sprinkler nozzle and water fog nozzle were studied. Seven of the tests carried out will be reported in this article. Language: en
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.