Abstract
Surface discharge on solid insulators is one of the significant issues in the development of vacuum circuit breakers (VCB) and vacuum interrupters (VI). We measured the charge activity on alumina dielectrics in vacuum through ultra-high speed and high sensitivity optical measurements. We identified the existence of charge activity with a small light emission on alumina dielectrics before the surface flashover development process, and defined this as a "pre-discharge" and measured its characteristics. We classified the charge activities into three processes: (1) pre-discharge, (2) surface flashover initiation, and (3) surface flashover expansion, in the development of surface discharge in vacuum. Utilizing this classification, we found that the surface predischarge in vacuum is generated by the electron emission from the cathode, and the subsequent flashover initiates with a steep increase in current and develops with the distortion of the electric field due to transiently-formed charging on the alumina dielectrics in vacuum.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.