Abstract

Noise caused by mechanical ventilation systems in dwellings remains a common problem in practice. To help designers and installers, a simplified acoustic calculation tool has been developed which can be used without detailed acoustic knowledge. The tool is based on the prediction models in EN 12354-5 and VDI 2081 and takes into account the airborne duct sound. The model has been validated by multiple case studies in dwellings. For each case study, the noise levels and airflow rates of the mechanical ventilation system have been measured in each room. Generally, the global A-weighted noise level is predicted with an accuracy of ± 3 dB, on the condition that the airborne duct sound is dominant and sufficiently accurate acoustical input data are available for key components like fans, silencers and air openings. However, some measurement results cannot be predicted by the simplified calculation framework, e.g. when turbulence in two closely placed fittings leads to additional flow noise. The uncertainty also increases when the fan sound is dominated by tonal components.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.