Abstract

A procedure based on the finite element method (FEM) is presented to determine the strongly distorted wave-forms of the magnetizing currents having given direct current (dc) components in each phase of a three-phase power transformer. The three phase voltages forming a symmetric sinusoidal system are assumed to be known. The relationships between the flux linkages of the three windings and the three values of the magnetizing current are determined using FEM and assuming static conditions. Suitable techniques are employed to establish the dependence of the dc components of the three magnetizing currents upon the three bias fluxes. The flux bias values yielding the given dc components are hence obtained by an iterative method yielding the wave-forms of the magnetizing currents having the prescribed dc values. The method is illustrated by a numerical example.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.