Abstract

AbstractThis paper presents the influence of latent heat load by changing the relative humidity of air flow distribution in the super‐heated gas region in an evaporator and the effect of the refrigerant flow path pattern. To estimate the influence, we applied the thermal network method that can consider refrigerant quality distribution in the heat exchanger. If the super‐heated gas region spreads to the upper wind row, humid air goes through the heat exchanger without drying, called “air flow bypass.” To suppress this phenomenon and simultaneously obtain the best performance, we chose an optimum path pattern on the basis of this method. As a result, the prediction shows that performance of the evaporator is recovered 5% for a simple 2‐row 2‐path heat exchanger when 40% of the unbalance of air flow rate occurs. © 2010 Wiley Periodicals, Inc. Heat Trans Asian Res; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/htj.20302

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call